Input Voltage AC |
230-400-500 V AC |
Output Voltage DC | 24 V DC |
Output Current | 7A |
Input Data | |
Nominal Input Voltage (2 x Vac) Manual select Input from 115 to 230 | 230 – 400 – 500 Vac |
Input Voltage Range (Vac) | 187 - 264 (230) 330 - 550 (400 - 500) |
Inrush Current (Vn and In Load) I 2t | ≤ 17A ≤ 5msec. |
Frequency | 47 – 63 Hz ±6% |
Input Current (115 – 230 Vac) | 1.5 - 0.8 - 0.7 A |
Internal Fuse | T 4 A |
External Fuse (recommended) | 10 A (MCBcurve B) |
Output Data | |
Output Voltage (Vn) Factory Setting ±3% | 24 Vdc |
Adjustment range (Vadj) | 22 - 27 Vdc |
Start up with Strong Load (capacitive load) | ≤50.000µ F |
Turn-On delay after applying mains voltage | 1 sec. (max) |
Continuous Current at 24 V < 40°C (In) | 7.5 A (permanent) |
Continuous Current at 24 V < 50°C (In) | 6 A (permanent) |
Continuous Current at 24 V < 60°C (In) | 5 A (permanent) |
Power Boost Current at 24 Vdc 60°C(In) | In (60°C) x 1.5 ≥ 3 min. |
Current max. Overload ≅ 4Vdc (permanent) | Imax=In60°Cx(1.8 - 2.2) |
Current Short Circuit Icc Max 2 sec.: Hiccup mode Permanent : Continuous Mode |
16 A |
Hold-up Time ( min. Vac) 12Vdc 5A | T yp. 20 msec |
Residual Ripple | ≤80 mVpp |
Efficiency | ≥ 91 % |
Over temperature Protection | Yes. Shut-down output and automatic restart. |
Short-circuit protection | 1° Hiccup Mode 2° Continuous mode 3° Manual Reset |
Dissipation power load max (W) | 17 |
Over Load protection | Yes |
Over Voltage Output protection | Yes (typ. 35 Vdc) |
Parallel connection | Yes |
Power Good Contact rating (EN60947.4.1): Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A Min.1mA at 5 Vdc |
Resistive load Min permissive load |
Ct