2-PHASE POWER SUPPLY 24V, 4.5A

SPP2-24120
Input Voltage AC

230-400-500 V AC    

Output Voltage DC 24 V DC
Output Current 4.5A
 Input Data
AC Input Voltage Range 85 VAC - 264 VAC
(Refer Derating Curve)
DC Input Voltage Range 120 VDC - 370 VDC
Nominal Input Voltage 115 VAC / 230 VAC
(165 VDC / 325 VDC)
Frequency 45 Hz ... 65Hz
Input Current  (115 – 230 Vac) 1.4 A (115 VAC)  0.8 A (230 VAC)
Internal Fuse T 4 A
External Fuse (recommended) 10 A (MCBcurve B)
Output Data
Output Voltage (Vn)  Factory Setting  ±3% 24 Vdc
Adjustment range (Vadj) 22 – 27 Vdc
Start up with Strong Load (capacitive load) ≤50.000µ F
Turn-On delay after applying mains voltage 1.5 sec. (max)
Rated Current at 24 V 50°C  (In) 2.5 A
Rated Current at 24 V 60°C  (In) 1.875 A
Rated Current at 24 V 70°C  (In) 1.25 A
Power Boost Current at 24 Vdc  60°C  (In) 2.5 A  ≥ 3 min.
Hold-up Time ( min. Vac)  12Vdc 5A 30 msec (230 VAC),
15 msec (115 VAC)
Residual Ripple 150 mVpp
Efficiency 87 %
Over temperature Protection Yes. Shut-down output and automatic restart.
Short-circuit protection Yes
Dissipation power load max (W) 8.9 W
Over Load protection Yes, Hiccup Mode
Over Voltage Output protection Yes (typ. 35 Vdc)
Parallel connection No
Series  connection Yes
Turn On Delay 1 Seconds
Rise Time 50 msec