Input Voltage AC |
85-264 V AC |
Input Voltage DC | 120-370 V DC |
Output Voltage DC | 24 V DC |
Output Current | 0.8A |
Input Data | |
AC Input Voltage Range | 85 VAC - 264 VAC (Refer Derating Curve) |
DC Input Voltage Range | 120 VDC - 370 VDC |
Nominal Input Voltage | 115 VAC / 230 VAC (165 VDC / 325 VDC) |
Frequency | 45 Hz ... 65Hz |
Input Current (115 – 230 Vac) | 0.95 A (115 VAC) 0.55 A (230 VAC) |
Internal Fuse | T 4 A |
External Fuse (recommended) | 10 A (MCBcurve B) |
Output Data | |
Output Voltage (Vn) Factory Setting ±3% | 24 Vdc |
Adjustment range (Vadj) | 22 – 27 Vdc |
Start up with Strong Load (capacitive load) | ≤50.000µ F |
Turn-On delay after applying mains voltage | 1.5 sec. (max) |
Rated Current at 24 V 50°C (In) | 1.875 A |
Rated Current at 24 V 60°C (In) | 1.41 A |
Rated Current at 24 V 70°C (In) | 0.94 A |
Power Boost Current at 24 Vdc 60°C (In) | 1.75 A 3 min. |
Hold-up Time ( min. Vac) 12Vdc 5A | ≥ 30 msec (230 VAC), 15 msec (115 VAC) |
Residual Ripple | ≤150 mVpp |
Efficiency | ≥ 87 % |
Over temperature Protection | Yes. Shut-down output and automatic restart. |
Short-circuit protection | Yes |
Dissipation power load max (W) | 6.2 W |
Over Load protection | Yes, Hiccup Mode |
Over Voltage Output protection | Yes (typ. 35 Vdc) |
Parallel connection | No |
Series connection | Yes |
Turn On Delay | 1 Seconds |
Rise Time | 50 msec |
Ct